Specifications

ConnectCommunicationWiresinInstallationswithout
PDU
Maintenance
Bypass Panel
UPS
XR Battery
Enclosure
XR Battery
Enclosure
XR Battery
Enclosure
XR Battery
Enclosure
0P3199
0P4123
1
2
3
3
3
1
1
2
4
5
6
7
8
Front
1.RoutethebatterybreakertripcablefromJ1inthefirstXRBatteryEnclosuretoJ3inthenextXR
BatteryEnclosure.RepeattheprocedureforallXRBatteryEnclosures.
2.RoutethebatterybreakertripcablefromJ1inthelastXRBatteryEnclosuretoJ27onthe
EPO/ancillaryinterfaceboard(0P4123)intheUPS(forremoteXRBatteryEnclosurethelenght
ofthesignalmustnotexceed200m).
3.RoutethecommunicationcablefromXRCommunicationsport1ineachXRBatteryEnclosureto
port2inthenextXRBatteryEnclosure.Removetheterminatorwhennecessary.
4.RoutethecommunicationcablefromXRCommunicationsport1inthelastXRBatteryEnclosure
totheUPSXRCommunicationsport2(forremoteXRBatteryEnclosurethelenghtofthesignal
mustnotexceed200m).
5.Routethecommunicationcablesfromthemaintenancebypasspaneltothemaintenancebypass
interfaceboard(0P3199)intheUPS.Refertothewiringdiagramonthenextpageforconnection
information.
6.Ininstallationswithexternalswitchgear,removejumperwireharnessbetweenJ1andJ2.
7.Ininstallationswithoutanyswitchgear,installjumperwireharnessbetweenJ1andJ2.
8.Removethejumperbetweenpins13and14inJ2ininstallationswithoutPDU.
42
SymmetraPX100kW208V
990–3659C-001