Specifications
6.ConnecttheequipmentgroundingcableintheXRBatteryEnclosurethatisfarthestfromtheUPS.
RouteitthrougheachXRBatteryEnclosuretotheUPSthroughtheside,top,orbottom.
XR Output (to UPS or next XR)
BAT+
BAT-
CT (Midpoint)
BAT+
BAT-
CT (Midpoint)
XR Input (from XR)
Protection
device
Breaker
Fuse
Protection
device
Terminal
XR no. 1
XR no. 2
XR no. 3
XR no. 4
UPS
7.SettheenclosureaddressonthefrontsideofeachXRBatteryEnclosureandPDU/XRfrontside.
ConnecttheBatteryCablestotheUPS
Thecablescanberoutedthroughtheside,top,orbottom.
APCrecommendsusinga45ºcablelug.Ifyouusestraightcablelugs,
installabusbarsafetybracketbetweeneachbusbarandcablelugto
ensureasafemeasureofseparation.Thebracketsareprovidedwith
theUPS.
45
o
Safety
Bracket
Note:Donotremovethe12pcsM10nylonhexboltsfromthebusbars.Mountthecablesin
theopenholes.
Note:TheM10bolts,washers,andcabletiesaresuppliedintheUPSaccessorykit.
Note:Theprocedurebelowshowshowtoconnectthebatterycablesinsystemswithside
cableentry.Intoporbottomcableentrysystems,runthecablestoeitherthetoporthe
bottomandconnectthemtothebusbarsaccordingtothelabels.
990–3659C-001
SymmetraPX100kW208V
37