Specifications
BatteryCables
InstalltheAPCBatterySolution
TheSymmetraPX100kWUPScanmonitoruptofourAPCXRBatteryEnclosures.
Caution:Thesystemacceptsupto300kcmilcables.Thepowerterminalboltdiameteris
10mmandtherequiredtorquevalueis26Nm.
Note:Ininstallationswithnon-APCbatteries,followthedocumentationprovidedwiththe
batteries.
Note:Inremoteinstallations,panelsshouldbeinstalledonfreeends(partnumber
0M-7171D).
ConnecttheBatteryCablesbetweentheXRBatteryEnclosures
WARNING:ForremoteXRBatteryEnclosures,thelenghtofthesignalandpower
cablesmustnotexceed200m,onthecablethatconnectstheXRBatteryEnclosure
totheUPS.Forpowercablesbetween50and200m,thevoltagedropmustbetaken
intoaccountwhenthecablesizeischosen.
1.Intopentrysystems,loosenthetwotopboltsandremovetheeightlowerboltsfromtheupper
coverplate.Lifttheplatetoremoveit.
2.Loosenthetwotopboltsandremovetheeightlowerboltsfromthelowercoverplate.Liftthe
platetoremoveit.
3.UnwindthecablesincludedineachXRBatteryEnclosure.Removethecablelugsfromthecables
thatwillconnecttootherXRBatteryEnclosures.ForthecablesthatwillconnecttotheUPS,cut
offthecablelugontheendthatwillbemountedintheXRBatteryEnclosure.
990–3659C-001
SymmetraPX100kW208V
35