Specifications

ConnectPowerConductorsbetweentheUPSandthe
PDU(ApplicabletoallSystemswithPDU)
1.OpenthereardoorsofthePDUandtheUPS.
2.RemovethecoverfromthePDUtogetaccessto
thepowerconductors.UseaPhillipsscrewdriver
toremovethecaptivepanelfasteners.
3.Beforerunningtheconductors,loosenthethree
fastenersoneachUPSconductorreliefnextto
thePDU.
4.Cuttheconductortiesandroutetheoutputand
bypass/inputconductors(inputinsingleutility
systemsandbypassindualutilitysystems)to
theUPSthroughtheconductorreliefs.Lay
theconductorsneatlytominimizeconductor
build-up.
5.Connecttheoutputandbypass/inputconductors
fromthePDU.
6.Indualutilitysystems,connecttheinput
conductorstotheinputbusbars(L1,L2,L3).
7.Tightenthethreefastenersoneachconductor
relief.
8.ReinstallthecoverinthePDUandclosethe
reardoors.
RearofthePDU
2
RearoftheSystem
3
4
5
6
7
4
5
Input L1
Input L2
Input L3
BAT +
BAT -
CT (Midpoint)
Neutral
Output L1
Output L2
Output L3
Neutral
Bypass L1
Bypass L2
Bypass L3
Dual
Utility
Single
Utility
Neutral
Output L1
Output L2
Output L3
Input L1
Input L2
Input L3
Neutral
BAT +
BAT -
CT (Midpoint)
32
SymmetraPX100kW208V
990–3659C-001