Specifications
ConnectPowerConductorsinInstallationswithPDU
withoutTransformer—TopCableEntry
Caution:Ensureclockwisephaserotationandneutrallocationofthepowerterminalbolt.
Therequiredtorquevalueis31Nm.
FrontofthePDU
L1
N
L3
L2
Q1 = singleQ5 = dual
Q5 = dual
Q1 = single
(default)
Input
(single or dual
mains)
Dual cable ligs in
208 V PDU
1
2
3
4
2
4
1.Routetheconductors(inputconductorsinsingleutilitysystemsorbypassconductorsindual
utilitysystems)throughthetopofthePDU.
2.Connecttheinput/bypassconductorstotheL1,L2,L3,Nterminals.Note:Fora208VPDU,
installthecablesonthefrontholeofthedualcablelugs.
3.ConnecttheEquipmentGroundConductor(EGC)totheEGCterminal.
4.Indualutilitysystems,removetheplateandswitchthecablesaroundtohaveQ1inthebottomand
Q5atthetop.UseaPhillipsscrewdrivertoremovethecaptivepanelfasteners.Reinstalltheplate.
30
SymmetraPX100kW208V