Specifications
3.TakethecablesthatarepreinstalledintheSide
Carandroutethemthroughtheleftorrightside
(dependingonconfiguration)intothePDU.
4.Routetheconductors(inputconductorsinsingle
utilitysystemsorbypassconductorsindual
utilitysystems)throughthetopofthePDUin
topcableentrysystemsorthroughthesidefrom
theSideCarinbottomcableentrysystems.
5.Connecttheinput/bypassconductorstotheL1,
L2,L3,GroundingElectrodeConductor(GEC)
terminals.Note:Fora208VPDU,installthe
cablesonthefrontholeofthedualcablelugs.
6.ConnecttheEquipmentGroundConductor
(EGC)totheterminal.
7.Indualutilitysystems,removetheplateand
switchthecablesaroundtohaveQ1inthe
bottomandQ5atthetop.UseaPhillips
screwdrivertoremovethecaptivepanel
fasteners.Reinstalltheplate.
FrontoftheSideCar
3
3
FrontofthePDU
L1
L2
L3
Q3
Q2
Q1 = single
Q5 = dual
Q1 = single (default)
Q5 = dual
Input (single or dual mains)
From side car
From side car
4
4
4
5
6
7
7
5
990–3659C-001
SymmetraPX100kW208V
29