Specifications
ConnectPowerConductorsinInstallationswithout
PDU
Caution:Ensureclockwisephaserotationandneutrallocation.Thepowerterminalbolt
diameteris10mm.Therequiredtorquevalueis26Nm.
1.Routetheconductorsthroughtoporbottomof
theenclosure.
2.Insingleutilitysystems,installthethreecables
(0W3617)includedwiththeunit.BypassL3
toInputL3,BypassL2toInputL2andBypass
L1toInputL1.
3.Connecttheinputconductorstotheinput
busbars(L1,L2,L3,N).
4.Connecttheoutputconductorstotheoutput
busbars(L1,L2,L3,N).
5.Indualutilitysystems,connectthebypass
conductorstothebypassbusbars(L1,L2,L3).
6.ConnectthePEcableintheUPSaccordingto
thesymbolonthegroundingrail.
RearoftheUPS
Bypass L1
Bypass L2
Bypass L3
Output L1
Output L2
Output L3
PE
Neutral
Input L1
Input L2
Input L3
Neutral
1
2
3
4
5
6
1
990–3659C-001
SymmetraPX100kW208V
27