User guide
User Guide InfraStruxure 150kVA Power Distribution Unit 86
Configure event actions
Notification Parameters. For events that have an associated clearing event, you can also set the
following parameters as you configure events individually or by group, as described in the next two
sections. To access the parameters, click the receiver or recipient name.
Configure by event. To define event actions for an individual event:
1. Select the Administration tab, Notification on the top menu bar, and by event under Event
Actions on the left navigation menu.
2. In the list of events, review the marked columns to see whether the action you want is already
configured. (By default, logging is configured for all events.)
3. To view or change the current configuration, such as recipients to be notified by e-mail, or
Network Management Systems (NMSs) to be notified by SNMP traps, click on the event name.
Note: If no Syslog server is configured, items related to Syslog configuration are not displayed.
When viewing details of an event’s configuration, you can change the configuration, enable or disable
event logging or Syslog, or disable notification for specific e-mail recipients or trap receivers, but you
cannot add or remove recipients or receivers. To add or remove recipients or receivers, see the following:
• “Identifying Syslog Servers” on page 90
• “E-mail recipients” on page 88
• “Trap Receivers” on page 89
Configure by group. To configure a group of events simultaneously:
1. Select the Administration tab, Notification on the top menu bar, and by group under Event
Actions on the left navigation menu.
2. Choose how to group events for configuration:
– Choose Grouped by severity, and then select all events of one or more severity levels. You
cannot change the severity of an event.
– Choose Grouped by category, then select all events in one or more pre-defined categories.
3. Click Next>> to move from page to page to do the following:
a. Select event actions for the group of events.
• To choose any action except Logging (the default), you must first have at least one
relevant recipient or receiver configured.
• If you choose Logging and have configured a Syslog server, select Event Log or Syslog
(or both) on the next page.
b. Select whether to leave the newly configured event action enabled for this group of events
or to disable the action.
Parameter Description
Delay x time before sending If the event persists for the specified time, notification is sent. If the condition
clears before the time expires, no notification is sent.
Repeat at an interval of x time The notification is sent at the specified interval (e.g., every 2 minutes).
Up to x times During an active event, the notification repeats for this number of times.
Until condition clears The notification is sent repeatedly until the condition clears or is resolved.