User guide

User Guide InfraStruxure 150kVA Power Distribution Unit 66
View and edit branch circuit breaker settings
Path: Power Distribution > Panel # > even/odd
Select a group of circuit breakers (Panel 1 [01..42] [even|odd], Panel 2 [01..42] [even|odd]) to view the
following data:
Pos: The position of the breaker on the circuit breaker panel.
Rating: The rating of the breaker occupying this panel position, in amps.
Status: The state of the breaker.
Normal: The breaker is operating normally.
Warning: The low or high rating threshold has been violated.
Critical: The minimum or maximum rating threshold has been violated.
Name: A descriptive name for the breaker.
Current: The measured root mean square (RMS) current of the panel position.
To edit the name, or rating of a branch circuit breaker, select the text to modify. In the configuration page
that opens, type your changes in the text field and click Apply.
To edit threshold settings for a branch circuit breaker, select its name, then select Rating. Mark or clear
the check box for each threshold to define whether that threshold will generate breaker alarms. Define
each threshold as a percentage of the rated current, then click Apply.
To delete a breaker or group, click Delete Group at the bottom of this page.