User guide

57User Guide InfraStruxure 150kVA Power Distribution Unit
orNormal
Access: Administrator, Device
Description: Configure the normal state of the targeted output relay. The output relay will remain in
the normal state until a condition occurs that causes the output relay to change to the state opposite the
normal state.
Parameters: <normal state>
normal state = open|closed.
Example:
apc> orTarget 1
1. Output Relay 1,Closed
apc> orStatus
1. Output Relay 1,Closed
2. Output Relay 2,Closed
3. Output Relay 3,Closed
4. Output Relay 4,Closed
apc> orNormal open
1. Output Relay 1,Open
apc> orStatus
1. Output Relay 1,Open
2. Output Relay 2,Closed
3. Output Relay 3,Closed
4. Output Relay 4,Closed
orBrkrxxx
Access: Administrator, Device
Description: This category of alarm mapping commands associates any module threshold alarm with
the output relay/relays designated in the parameters.
With no parameter, display the currently associated output relays.
Output relay power distribution breaker alarm association commands:
orBrkrMxI
orBrkrHiI
orBrkrLoI
orBrkrMnI
orBrkrPos
Parameters: [<relay> <enable|disable>]
relay = output relay to be triggered(normally 1|2|3|4).
Example:
apc> orpdBrkrPos
1. Breaker Modules,Breaker Position,1,disable,2,disable,3,disable,4,disable
apc> orpdBrkrPos 2 enable
1. BreakerModules,Breaker Position,1,disable,2,enable,3,disable,4,disable
apc> orpdBrkrPos
1. Breaker Module,Breaker Position,1,disable,2,enable,3,disable,4,disable