User guide

53User Guide InfraStruxure 150kVA Power Distribution Unit
icStatus
Access: Administrator, Device
Description: Display input contact, alarm status, alarm severity, alarm enable, contact state and
location of each input contact in the PDU.
Example:
apc> icStatus
1. User Contact 1,Normal,Critical,Enable,Open,Location 1
2. User Contact 2,Normal,Warning,Enable,Open,Location 2
3. User Contact 3,Normal,Warning,Enable,Open,Location 3
4. User Contact 4,Normal,Warning,Enable,Open,Location 4
icTarget
Access: Administrator, Device
Description: Selects input contact for configuration.
Parameters: <contact>
Contact = input contact of interest.
Example:
apc> Target 1
1. User Contact 1,Normal,Critical,Enable,Open,Location 1
icName
Access: Administrator, Device
Description: Configure the name of the targeted input contact.
Parameters: <name>
name = character string of up to 20 characters.
Example:
apc> icStatus
1. New Contact 1,Normal,Critica,Enable,Open,Location 1
2. User Contact 2,Normal,Warning,Enable,Open,Location 2
3. User Contact 3,Normal,Warning,Enable,Open,Location 3
4. User Contact 4,Normal,Critical,Enable,Open,Location 4
apc> icName "New Contact 1"
1. New Contact 1,Normal,Critical,Enable,Open,Location 1
apc> icStatus
1. New Contact 1,Normal,Critical,Enable,Open,Location 1
2. User Contact 2,Normal,Warning,Enable,Open,Location 2
3. User Contact 3,Normal,Warning,Enable,Open,Location 3
4. User Contact 4,Normal,Critical,Enable,Open,Location 4