User guide
45User Guide InfraStruxure 150kVA Power Distribution Unit
brkrAlrm
Access: Administrator, Device
Description. Enables alarm generation on the cable breaker selected by the brkrTarget and brkrPanel
commands.
The response contains 1 line containing the panel.breaker, followed by the alarm thresholds and enables.
Parameters: <switch> (switch=enable|disable)
Example:
apc> brkrstatus 2
1. 1.2,Newname 1.2,Newloc 1.2,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/
2012
2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3%
3. 1.2,Disable,80%,24A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable
apc> brkralrm enable
1. 1.2,Enable,80%,24A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable
Error Messages: E102