User guide
43User Guide InfraStruxure 150kVA Power Distribution Unit
Example:
apc>brkrStatus
1. 1.1,pb1-1,Unknown,,20A,50A,Normal,0.0kW,1.7kWh,08/01/2012
2. 1.1,L1,0.0A,0.0%,1.3,L2,0.0A,0.0%,1.5,L3,0.0A,0.0%
3. 1.7,pb1-7,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
4. 1.7,L1,0.0A,0.0%,1.9,L2,0.0A,0.0%,1.11,L3,0.0A,0.0%
5. 1.13,pb1-13,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
6. 1.13,L1,0.0A,0.0%,1.15,L2,0.0A,0.0%,1.17,L3,0.0A,0.0%
7. 1.21,pb1-21,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
8. 1.21,L2,0.0A,0.0%,1.23,L3,0.0A,0.0%
9. 1.25,pb1-25,Unknown,,20A,50A,Normal,0.0kW,0.0kWh,08/01/2012
10. 1.25,L1,0.0A,0.0%,1.27,L2,0.0A,0.0%
11. 1.31,pb1-31,Unknown,,50A,50A,Normal,0.0kW,0.0kWh,08/01/2012
12. 1.31,L1,0.0A,0.0%,1.33,L2,0.0A,0.0%,1.35,L3,0.0A,0.0%
13. 1.37,pb1-37,Unknown,,60A,100A,Normal,0.0kW,0.0kWh,08/01/2012
14. 1.37,L1,0.0A,0.0%,1.39,L2,0.0A,0.0%,1.41,L3,0.0A,0.0%
apc>brkrStatus
1. 1.2,pb1-2,Unknown,,15A,50A,Normal,0.0kW,0.0kWh,08/01/2012
2. 1.2,L1,0.0A,0.0%,1.4,L2,0.0A,0.0%
3. 1.8,pb1-8,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
4. 1.8,L1,0.0A,0.0%
5. 1.10,pb1-10,Unknown,,20A,50A,Normal,0.0kW,0.0kWh,08/01/2012
6. 1.10,L2,0.0A,0.0%
7. 1.12,pb1-12,Unknown,,15A,50A,Normal,0.0kW,0.0kWh,08/01/2012
8. 1.12,L3,0.0A,0.0%
9. 1.14,pb1-14,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
10. 1.14,L1,0.0A,0.0%,1.16,L2,0.0A,0.0%
11. 1.18,pb1-18,Unknown,,20A,50A,Normal,0.0kW,0.0kWh,08/01/2012
12. 1.18,L3,0.0A,0.0%,1.20,L1,0.0A,0.0%
13. 1.26,pb1-26,Unknown,,60A,100A,Normal,0.0kW,0.0kWh,08/01/2012
14. 1.26,L1,0.0A,0.0%,1.28,L2,0.0A,0.0%,1.30,L3,0.0A,0.0%
15. 1.32,pb1-32,Unknown,,50A,50A,Normal,0.0kW,0.0kWh,08/01/2012
16. 1.32,L1,0.0A,0.0%,1.34,L2,0.0A,0.0%,1.36,L3,0.0A,0.0%
17. 1.38,pb1-38,Unknown,,60A,100A,Normal,0.0kW,0.0kWh,08/01/2012
18. 1.38,L1,0.0A,0.0%,1.40,L2,0.0A,0.0%,1.42,L3,0.0A,0.0%
Error Messages: E102
brkrTarget
Access: Administrator, Device
Description. Select the breaker on the panel designated by the previous brkrPanel to be configured. By
selecting a single target for configuration, there is no breaker number required in each of the
configuration commands.
The response to the brkrTarget command is the same as the brkrStatus command with a parameter.
Parameters: <breaker> (breaker=breaker # of interest)
Example:
apc> brkrTarget 2
1. 1.2,Unknown,Unknown,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/2012
2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3%
3. 1.2,Disable,80%,24A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable
Error Messages: E102