User guide
User Guide InfraStruxure 150kVA Power Distribution Unit 42
brkrPanel
Access: Administrator, Device
Description. Select the panel containing the breaker to access. The response to a brkrPanel selection is
to display the following information, two lines per breaker. The first line contains panel, breaker, breaker
name, breaker location, breaker cable description, breaker rating, corresponding CT rating, alarm status,
power, energy consumption and date of last energy reset date. The second line contains panel, breaker,
phase, current and percent load for each phase spanned by the breaker, i.e. single phase breakers cover
one phase while three phase breakers cover three phases.
Parameters: 1|2
Example:
apc>brkrPanel 1
1. 1.2,pb1-2,Unknown,,15A,50A,Normal,0.0kW,0.0kWh,08/01/2012
2. 1.2,L1,0.0A,0.0%,1.4,L2,0.0A,0.0%
3. 1.8,pb1-8,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
4. 1.8,L1,0.0A,0.0%
5. 1.10,pb1-10,Unknown,,20A,50A,Normal,0.0kW,0.0kWh,08/01/2012
6. 1.10,L2,0.0A,0.0%
7. 1.12,pb1-12,Unknown,,15A,50A,Normal,0.0kW,0.0kWh,08/01/2012
8. 1.12,L3,0.0A,0.0%
9. 1.14,pb1-14,Unknown,,30A,50A,Normal,0.0kW,0.0kWh,08/01/2012
10. 1.14,L1,0.0A,0.0%,1.16,L2,0.0A,0.0%
11. 1.18,pb1-18,Unknown,,20A,50A,Normal,0.0kW,0.0kWh,08/01/2012
12. 1.18,L3,0.0A,0.0%,1.20,L1,0.0A,0.0%
13. 1.26,pb1-26,Unknown,,60A,100A,Normal,0.0kW,0.0kWh,08/01/2012
14. 1.26,L1,0.0A,0.0%,1.28,L2,0.0A,0.0%,1.30,L3,0.0A,0.0%
15. 1.32,pb1-32,Unknown,,50A,50A,Normal,0.0kW,0.0kWh,08/01/2012
16. 1.32,L1,0.0A,0.0%,1.34,L2,0.0A,0.0%,1.36,L3,0.0A,0.0%
17. 1.38,pb1-38,Unknown,,60A,100A,Normal,0.0kW,0.0kWh,08/01/2012
18. 1.38,L1,0.0A,0.0%,1.40,L2,0.0A,0.0%,1.42,L3,0.0A,0.0%
apc>
brkrStatus
Access: Administrator, Device
Description. The brkrStatus command with no parameter displays alternatively the even or odd
numbered breakers in the panel indicated by the previous brkrPanel. Repeating the brkrStatus command
will display the other side of the panel. The first line of the response contains the panel.breaker, breaker
name, breaker location, breaker cable description, breaker rating, corresponding CT rating, alarm status,
power, energy consumed and date of last energy reset. The second line contains the panel.breaker, phase,
current and percent load for each phase spanned by the breaker.
The "brkrStatus x" command acts on the last selected panel, until changed with the "brkrPanel x"
command
The brkrStatus command with a parameter displays the data for the breaker indicated by the parameter.
This response generates three lines, the first two as described above and the third contains panel.breaker,
alarm enable, maximum current threshold, max current threshold enable, high current threshold, hi
current threshold enable, low current threshold, lo current threshold enable, minimum current threshold
and min current threshold enable.
Parameters: <breaker> (breaker = breaker # of interest)