41User Guide InfraStruxure 150kVA Power Distribution Unit
subfdBrkr
Access: Administrator, Device
Description: Configure the breaker position critical alarm for the target subfeed.
Parameters: [<enable|disable>]
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdBrkr disable
1. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
subfdRstkWh
Access: Administrator, Device
Description: Reset the energy usage and usage date for the target subfeed.
subfdTarget 1 = Panel board 1
subfdTarget 2 = Panel board 2
subfdTarget 3 = Subfeed
Example:
apc> subfdTarget 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdRstkWh
1. Normal,Open,160A,0kWh,12/27/2012
apc> subfdTarget 1
1. Normal,Open,160A,0kWh,12/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable