User guide

User Guide InfraStruxure 150kVA Power Distribution Unit 40
subfdThrLo
Access: Administrator, Device
Description: Configure the low load alarm threshold and warning alarm for the target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,20%,Disable,10%,Disable
apc> subfdThrLo 25 enable
1. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
subfdThrMn
Access: Administrator, Device
Description: Configure the minimum load alarm threshold and critical alarm for target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
apc> subfdThrMn 5 enable
1. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable