User guide
User Guide InfraStruxure 150kVA Power Distribution Unit 38
subfdLoc
Access: Administrator, Device
Description: Configure the location of the targeted subfeed.
Parameters: [<location>]
location = a string of up to 20 characters
Example:
apc> subfdTarget 1
1. Enable,Enable,89%,Enable,72%,Enable,30%,Enable,20%,Disable
2. Open,Critical,160A,765kWh,10/27/2012
apc> subfdStatus
1. Panel 1, Normal,0.0kW,Sub Location 1
2. Panel 2, Normal,0.0kW,Sub Location 2
3. Subfeed, Normal,0.0kW,Sub Location 3
apc> subfdLoc "New Location 1"
1. Panel 1, Normal,0.0kW,New Location 1
apc> subfdStatus
1. Panel 1, Normal,0.0kW,New Location 1
2. Panel 2, Normal,0.0kW,Sub Location 2
3. Subfeed, Normal,0.0kW,Sub Location 3
subfdAlarm
Access: Administrator, Device
Description: Enable or disable alarm generation by target subfeed.
Parameters: <enable|disable>
Example:
apc> subfdTarget 1
1. Enable,Enable,89%,Enable,72%,Enable,30%,Enable,20%,Disable
2. Open,Critical,160A,765kWh,10/27/2012
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Enable,Enable,90%,Disable,70%,Disable,20%,Disable,10%,Disable
apc> subfdAlarm disable
1. Disable,Enable,90%,Disable,70%,Disable,20%,Disable,10%,Disable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,90%,Disable,70%,Disable,20%,Disable,10%,Disable