37User Guide InfraStruxure 150kVA Power Distribution Unit
subfdStatus
Access: Administrator, Device
Description: If no parameter is entered, the status of the subfeeds is displayed (name, alarm condition,
power and location). If a parameter is entered, the alarm status, subfeed breaker position, breaker rating,
energy usage and date last reset are displayed. Current, percent of capacity, power and current alarm per
phase are also displayed.
Parameters: [<subfeed>]
Subfeed = 1 to number of subfeeds.
No parameter indicates all subfeeds and yields abbreviated status.
Example:
apc> subfdStatus
1. Panel 1,Normal,0.0kW,Sub Location 1
2. Panel 2,Normal,0.0kW,Sub Location 2
3. Subfeed,Normal,0.0kW,Sub Location 3
apc> subfdStatus 1
1. Open, Normal, 165A to 225A,765kWh,10/27/2012
2. 0.0A,0%,0.0kW,None,0.0A,0%,0.0kW,None,0.0A,0%,0.0kW,None
subfdTarget
Access: Administrator, Device
Description: Selects a subfeed as the target for configuration and displays subfeed details: individual
phase threshold values and threshold enables, as well as the subfeed breaker position, breaker alarm,
breaker rating, energy usage and date last reset.
Power distribution is accomplished through two breaker panels and one subfeed. In this application,
subfeed #1 monitors distribution panel 1, subfeed #2 monitors distribution panel 2 and subfeed #3
monitors the distribution subfeed. The above indicators are the parameter for this command.
Parameters: [<subfeed>]
Subfeed = subfeed of interest. Default is 0, so parameter is required.
1 = distribution Panel 1, 2 = distribution Panel 2, 3 = distribution subfeed.
Example:
apc> subfdTarget 1
1. Enable,Enable,89%,Enable,72%,Enable,30%,Enable,20%,Disable
2. Open,Critical,160A,765kWh,10/27/2012