User guide
User Guide InfraStruxure 150kVA Power Distribution Unit 36
sysThrLoI
Access: Administrator, Device
Description: Configure the low current alarm threshold and enable a corresponding warning alarm.
Parameters: [<fraction>] [<enable|disable>]
Fraction = percent of rated current.
Example:
apc> sysThrLoI
1. 0%,Disable
apc> sysThrLoI 30 Enable
1. 30%,Enable
apc> sysThrLoI
1. 30%,Enable
sysThrMnI
Access: Administrator, Device
Description: Configure the low current alarm threshold and enable a corresponding warning alarm.
Parameters: [<fraction>] [<enable|disable>]
Fraction = percent of rated current.
Example:
apc> sysAlrmCfg
1.0%,Disable
apc> sysThrMnI 10 Enable
1. 10%,Enable
apc> sysAlrmCfg
1. 10%,Enable
sysFreqDev
Access: Administrator, Device
Description: Configure the frequency deviation threshold and enable a corresponding warning alarm.
Input is either a deviation value or disable.
Parameters: [<Deviation >]
Deviation = disable,0.2, 0.5, 1.0, 1.5, 20.,3.0, 4.0, 5.0, 9.0 Hz
Example:
apc> sysAlrmCfg
1. MaxV,+25%,Enable,HiV, +15%,Enable,LoV,-15%,Enable,MinV,-25%,Enable
2. MaxA,90%,Enable,HiA,80%,Enable,LoA,30%,Enable,MinA,10%,Enable,Freq,
Disable
apc> sysFreqDev 1.0
1. 1.0
apc> sysAlrmCfg
1. MaxV,+25%,Enable,HiV, +15%,Enable,LoV,-15%,Eable,MinV,-25%,Enable
2.
MaxA,90%,Enable,HiA,80%,Enable,LoA30%,Enable,MinA,10%,Enable,Freq,1.0,
Enable