User Guide InfraStruxure 150kVA Power Distribution Unit 34
sysThrMxV
Access: Administrator, Device
Description: Configure the maximum voltage (L-N) alarm threshold and enable corresponding critical
alarm. Parameters: [<fraction>] [<enable|disable>]
Fraction = percent above device nominal voltage.
Example:
apc> sysAlrmCfg
1. MaxV,+20%,Disable,HiV,+12%,Disable,LoV,-12%,Disable,MinV,-20%,Disable
2. MaxA,0%,Disable,HiA,0%,Disable,LoA,0%,Disable,MinA,0%,Disable,Freq,
Disable
apc> sysThrMxV 25 Enable
1. 25%,Enable
apc> sysAlrmCfg
1. MaxV,25% ,Enable,HiV, +12%,Disable,LoV,-12%,Disable,MinV,-20%,Disable
2. MaxA,90%,Disable,HiA,80%,Disable,LoA,0%,Disable,MinA,0%,Disable,Freq,
Disable
sysThrHiV
Access: Administrator, Device
Description: Configure the high voltage (L-N) alarm threshold and enable a corresponding warning
alarm. Note the status version of the command. Parameters: [<fraction>] [<enable|disable>]
Fraction = percent above device nominal voltage.
Example:
apc> sysThrHiV
1. 12%,Disable
apc> sysThrHiV 15 Enable
1. 15%,Disable
apc> sysThrHiV
E000: Success
1. 15%,Enable
sysThrLoV
Access: Administrator, Device
Description: Configure the low voltage (L-N) alarm threshold and enable a corresponding warning
alarm. The minus sign is implied, not expressed. Parameters: [<fraction>] [<enable|disable>]
Fraction = percent below device nominal voltage.
Example:
apc> sysThrLoV
1. -12%,Disable
apc> sysThrLoV 15 Enable
1. -15%,Disable
apc> sysThrLoV
1. -15%,Enable