User guide
User Guide InfraStruxure 150kVA Power Distribution Unit 6
Local access to the command line interface
For local access, use a computer that connects to the PDU through the serial port to access the command
line interface:
1. Select a serial port at the computer and disable any service that uses the port.
2. Connect the provided serial cable (part number 940-0299) from the selected port on the computer
to the configuration port at the PDU.
3. Run a terminal program (e.g., HyperTerminal), and configure the selected port for 9600 bps, 8
data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER. At the prompts, enter your user name and password.
Main Screen
Example of the screen displayed when you log on to the command line interface of the PDU:
• Two fields identify the APC operating system (AOS) and application (APP) firmware versions.
The application firmware name identifies the PDU that connects to the network through this
NMC.
NMC AOS vx.x.x
x84P APP vx.x.x
• Three fields identify the system name, contact person, and location of the PDU. (In the Web
interface, select the Administration tab, General in the top menu bar, and Identification in the
left navigation menu to set these values.)
Name : Test Lab
Contact: Don Adams
Location: Building 3
• The Up Time field reports how long the PDU has been running since it was last turned on or reset.
Up Time: 7 Days 21 Hours 21 Minutes
• Two fields report when you logged in, by date and time.
Date : 07/30/2012
Time : 5:58:30
User Name : <admin or device Name>
Password : <admin or device Password>
American Power Conversion Network Management Card AOS vx.x.x
(c)Copyright 2011 All Rights Reserved x84P vx.x.x
--------------------------------------------------------------------------
Name : Test Lab Date : 07/30/2012
Contact : Don Adams Time : 5:58:30
Location : Building 3 User : Administrator
Up Time : 7 Days, 21 Hours, 21 Minutes Stat : P+ N4+ N6+ A+
Type ? for command listing
Use tcpip command for IP address(-i), subnet(-s), and gateway(-g)
apc>