User`s guide

®
USER’S GUIDE
Switched Rack PDU
10
Input Selector On 3-phase models, press the input selector to
monitor the current of the next phase or bank.
For either 1- or 3-phase units, press and hold the
input selector to display the IP address of the Rack
PDU or to invert the display. At five seconds, the IP
address is displayed; at ten seconds, the displayed
numbers invert.
10/100 Base-T Connector Connects the Rack PDU to the network.
Status LED See Status LED.
Link-RX/TX LED See Link-RX/TX (10/100) LED.
RJ-12 Serial Port Connects the Rack PDU to a terminal emulator
program for local access to the control console. Use
the supplied serial cable (APC part number
940-0144A).
Digital Display Displays the current (amps) for the phase or bank
indicated by the illuminated Load Indicator LED. On
3-phase models, the Digital Display will cycle
through the phases, banks, or outlets, displaying
the current for each for 3 seconds.
If an internal communication or power supply failure
occurs (for either a 1- or 3-phase model), the Digital
Display displays Er, which you can clear by
pressing the input selector.
Reset Button Resets the Rack PDU without affecting the outlet
status.
Item Function