User`s guide

®
USER’S GUIDE
Switched Rack PDU
109
address of 150.250.6.10.
ftp> open 150.250.6.10 21000
4. Log on using the Administrator user name and password. (apc is the default for
both.)
5. Upgrade the AOS. For example:
ftp> bin
ftp> put apc_hw02_aos_XXX.bin
6. When FTP confirms the transfer, type Quit to close the session.
7. Wait 20 seconds, and then repeat step 2 through step 6, but in step 5, use the
application module file name instead of the AOS module.
Instructions for using SCP. To use Secure CoPy (SCP) to upgrade the firmware for
one Rack PDU:
1. Identify and locate the firmware modules described in the preceding instructions for
FTP.
2. Use an SCP command line to transfer the AOS firmware module to the Rack PDU.
The following example assumes a Rack PDU IP address of 158.205.6.185, and an
AOS module of apc_hw02_aos_XXX.bin.)
scp apc_hw02_aos_XXX.bin apc@158.205.6.185:apc_hw02_aos_XXX.bin
3. Use a similar SCP command line, with the name of the application module instead
of the AOS module, to transfer the application module to the Rack PDU.
How to upgrade multiple Rack PDUs
Export configuration settings. You can create batch files and use an APC utility to
retrieve configuration settings from multiple Rack PDUs and export them to other Rack
PDUs.
See also
See Release Notes: ini File Utility, version 1.0 on the APC Switched
Rack PDU Utility CD.