Exporting the file to a single Rack PDU. To export the .ini file to another Switched
Rack PDU, use any of the file transfer protocols supported by Switched Rack PDUs
(including FTP, FTP Client, SCP, and TFTP). The following example uses FTP:
1. From the folder containing the customized .ini file and its copy, use FTP to log in to
the Rack PDU to which you are exporting the .ini file. For example:
ftp> open 158.165.4.135
2. Export the copy of the customized .ini file. The receiving Rack PDU accepts any file
name that has the .ini suffix, is no more than 64 characters in length, and is
exported to its root directory.
ftp> put filename.ini
Exporting the file to multiple Rack PDUs. To export the .ini file to multiple Switched
Rack PDUs:
Use FTP or SCP, but write a script that incorporates and repeats the steps used for
exporting the file to a single Management Card.
Use a batch processing file and the APC .ini file utility.
The Upload Event and Error Messages
The event and its error messages
The following system event occurs when the receiving Switched Rack PDU completes
using the .ini file to update its settings.
Configuration file upload complete, with number valid values
This event has no default severity level.
If a keyword, section name, or value is invalid, the event text is extended to include
notification of the following errors.
See also
To create the batch file and use the utility, see Release Notes: ini
File Utility, version 1.0 on the APC Switched Rack PDU Utility CD.