User`s guide

®
USER’S GUIDE
Network Management Card
93
Event Code (Converted
to Numeric Format) and
Event Name
Network Management Card
Code Event Codes Events
16 INTERNAL ZONE 0x031B
Environment: A critical fault exists for integrated Environmental
Monitor input contact {number} ({name} at {location}).
17 INTERNAL ZONE
CLEAR
0x031C
Environment: A fault no longer exists for integrated Environmental
Monitor input contact {number} ({name} at {location}).
18 INTERNAL
PROBE
0x031D
Environment: A low temperature threshold violation exists for
integrated Environmental Monitor sensor ({name} at {location})
reporting under {threshold}.
0x031F
Environment: A high temperature threshold violation exists for
integrated Environmental Monitor sensor ({name} at {location})
reporting over {threshold}.
0x0321
Environment: A low humidity threshold violation exists for
integrated Environmental Monitor sensor ({name} at {location})
reporting under {threshold}.
0x0323
Environment: A high humidity threshold violation exists for
integrated Environmental Monitor sensor ({name} at {location})
reporting over {threshold}.
19 INTERNAL
PROBE CLEAR
0x031E
Environment: A low temperature threshold violation no longer
exists for integrated Environmental Monitor sensor ({name} at
{location}).
0x0320
Environment: A high temperature threshold violation no longer
exists for integrated Environmental Monitor sensor ({name} at
{location}).
0x0322
Environment: A low humidity threshold violation no longer exists for
integrated Environmental Monitor sensor ({name} at {location}).
0x0324
Environment: A high humidity threshold violation no longer exists
for integrated Environmental Monitor sensor ({name} at {location}).
The Out-of-Band Management Card has no event codes or event names for these events generated by the
Integrated Environmental Monitor of an AP9618 or AP9619 Network Management Card.