One of the following event codes is sent when communication with the UPS is lost,
when the UPS switches to bypass mode, or when the UPS is overloaded.
One of the following event codes is sent when an external APC environmental
monitoring device or the Integrated Environmental Monitor of a Network Management
Card detects a problem or reports that a problem is resolved.
Out-of-Band Management Card Network Management Card
Code Event Code Event
6 LOST COM W/UPS 0x0102 UPS: Lost the local network management
interface-to-UPS communication.
7 BYPASS/OVERLOAD 0x0103 UPS: The load exceeds 100% of rated capacity.
0x011C UPS: In bypass in response to the UPS front-
panel or a user-initiated software command,
typically for maintenance.
0x011D UPS: In bypass in response to the bypass
switch at the UPS, typically for maintenance.
Out-of-Band
Management Card
Network Management Card
Code Event Codes Events for an Environmental Monitoring Card
8 ZONE 1 0x0301 Environment: A critical fault exists for external
Environmental Monitor input contact 1 ({name} at {location}).
9 ZONE 2 0x0303 Environment: A critical fault exists for external
Environmental Monitor input contact 2 ({name} at {location}).
10 ZONE 3 0x0305 Environment: A critical fault exists for external
Environmental Monitor input contact 3 ({name} at {location}).
11 ZONE 4 0x0307 Environment: A critical fault exists for external
Environmental Monitor input contact 4 ({name} at {location}).