Output Relay Option
Click Output Relay on the left navigation menu of the Environment tab to display the
status of the output relay and configure its values.
About
Click About on the left navigation menu of the Environment tab to display what
environmental monitors are in use with this UPS and their firmware versions
Parameter Description
Name A name for this output relay. Maximum: 20 characters.
Location The location of this output relay. Maximum: 20 characters.
Alarm
Status
Normal if this output relay is not reporting an alarm, or the severity of the alarm if
this output relay is reporting an alarm.
State The current state of this output relay: Closed or Open.
Normal
State
The normal (non-alarm) state of this output relay: Closed or Open.
Control To change the current state of this output relay, check-mark the setting.
Map Output
to
Select one or more options. For each option, the number of alarms selected from
the number available is in brackets. Click an option name to view available alarms
or to change the selection. When a selected alarm occurs, the output relay
changes to its alarm state.
Delay The number of seconds a selected alarm condition must exist before the output
relay is activated. Use this setting to avoid activating an alarm for brief transient
conditions.
N
OTE: Even if additional mapped alarms occur after the delay begins, the delay
does not restart but continues until the output relay is activated.
Hold The minimum number of seconds the output relay remains activated after the
alarm occurs. Even if the activating alarm condition is corrected, the output relay
remains activated until this time period expires.