User`s guide

®
USER’S GUIDE
Network Management Card
42
The settings option (including automatic load-shedding)
Click the name of an outlet group to view or configure its settings:
Setting or Field Description
Name A name for the outlet group (up to 20 characters) displayed with the outlet
group number wherever the interface displays that outlet group number.
State Displays the state of the outlet group (on or off).
Power On Delay When this outlet group is off, it waits this delay (up to 600 seconds) before
turning on when Delayed On, Reboot, or Delayed Reboot is selected as
the action. To override Power On Delay, mark the Never check-box. Only
the action Immediate On will turn outlets on when Never is marked.
Power Off Delay When this outlet group is on, it waits this delay (up to 600 seconds) before
turning off when Delayed Off, Reboot, or Delayed Reboot is selected as
the action. (During a delayed reboot, the outlet group then waits the number
of seconds configured as Reboot Duration and Power On Delay before it
turns on.)
Reboot Duration When this outlet group is on:
• If Reboot is selected as the action, the outlet group turns off immediately
and then waits this delay (up to 600 seconds) before turning on
• If Delayed Reboot is selected as the action, the outlet group waits these
three delays: Power Off Delay before turning off, and Reboot Duration
followed by Power on Delay before turning on.
Load Shedding Use these settings to provide automatic, sequenced, load-shedding when a
problem occurs with input voltage or battery capacity and to provide
automatic sequenced start-up of outlet groups when the problem is resolved.
Settings to turn this outlet group off:
• When a power failure is longer than the number of seconds you specify.
• When input power fails and the UPS battery capacity drops below the
percentage you specify.
• When the output drawn from the UPS exceeds the percentage of UPS
output overload you specify.
Settings to turn this outlet group on:
• When the outlet group has waited the number of seconds you specify.
• When the battery recharges to the percentage of full capacity you specify.