The reset UPS defaults option
Mark this check-box to reset all UPS configuration settings to their default values,
except UPS Name and Output Voltage. The time required to reset configuration
settings may be a minute or more.
The parallel units option (Smart-UPS VT, Silcon, and AIS 5000 UPSs)
The self-test schedule option
Use this option to define when the UPS will initiate a self-test (never, at start-up and
then weekly, at startup and every two weeks, or at start-up only). This option is not
available for Silcon and AIS 5000 UPSs.
Diagnostics
You can run these diagnostic tests for any APC UPS except a Silcon or AIS 5000 UPS:
Field or Setting Description
Parallel Unit
Configuration
Lists all parallel units (UPSs of the same type that share a load, continuing to
provide power to the load if a parallel unit fails). The UPS to which you are
logged on is first on the list.
Add Unit Use this button to add a unit (up to a maximum of nine) or to change the
name of a configured unit. Specify a name for the unit (up to 8 characters)
and specify its IP address.
Field Description
Self-test The result (passed, failed, or unavailable) and date of the last UPS self-test
Calibration The result of the last runtime calibration. A calibration recalculates remaining
runtime and requires the following:
• Because a calibration temporarily depletes the UPS batteries, you can perform a
calibration only if battery capacity is at 100%.
• For some UPSs, the load must be at least 7% for a calibration to be performed.