User`s guide
®
USER’S GUIDE
Network Management Card
33
.
Action Definition
Turn UPS
On
Turns on power at the UPS.
• For a UPS model with outlet groups, this action then turns on the outlet groups
according to the value for Power On Delay for each group. See The settings option
(including automatic load-shedding).
• For a Synchronized Control Group, after a delay of a few seconds, the action turns on
all enabled group members that have input power.
Turn UPS
Off
Turns off the output power of the UPS and (for a UPS model with outlet groups) of all its
outlet groups immediately, without a shutdown delay. The UPS and all its outlet groups
remain off until you turn on its power again.
For a Synchronized Control Group, this action turns off power at all enabled members of
the group. No Shutdown Delay value is used. The UPSs turn off after a few seconds and
remain off until you turn on their power. See The shutdown option.
N
OTE: For a synchronized turn-off action that uses the value of the Shutdown Delay of
the initiating UPS, use SNMP. For the upsAdvControlUpsOff OID, set the value
turnUpsSyncGroupOffAfterDelay (5).
Turn UPS
Off
Gracefully
(control
console)
Turns off outlet power of the UPS and (for a UPS model with outlet groups) all its outlet
groups after the Maximum Required Delay and the configured Shutdown Delay. See
The PowerChute Option.
For a Synchronized Control Group, the action uses the delays of the initiating UPS.