User`s guide

®
USER’S GUIDE
Network Management Card
32
In reboot and sleep actions:
Immediately before the initiating UPS begins waiting the time specified as Return
Delay, by default it waits up to 120 seconds (its configurable Power Synchronized
Delay) for any UPS that does not have input power to regain that power. Any UPS
that fails to regain input power during that delay does not participate in the
synchronized restart, but waits until its own input power returns before restarting.
The LEDs on the front of the UPS do not sequence their lights as they do for a
normal (not synchronized) reboot or sleep action.
UPS status and events are reported in the same way for synchronized actions as for
actions on individual UPSs.
Actions (for a single UPS and Synchronized Control Groups)
Use the actions described in the following table for individual UPSs and for
Synchronized Control Groups, within these guidelines:
All actions except Put UPS in Bypass and Take UPS Off Bypass are supported:
For Synchronized Control Groups of Symmetra UPS or Smart-UPS models
For all individual APC UPSs except Silcon UPS and AIS 5000 UPS models
Put UPS in Bypass and Take UPS Off Bypass are supported:
Only for individual UPSs, not for Synchronized Control Groups
Only for Matrix-UPS, Symmetra UPS, and some Smart-UPS models
To control a Silcon UPS or an AIS 5000 UPS, see Control options for
Silcon UPS and AIS 5000 UPS.
For more information about the delays and settings in the following table, see
Configuration Options and The Sync Control Option. To apply Test UPS
Alarm to a Synchronized Control Group, see Diagnostics.
When you select Yes for Signal PowerChute Server Shutdown in the Web
interface, initiating a Turn UPS Off, Reboot UPS, or Put UPS To Sleep
action is equivalent to selecting Turn UPS Off Gracefully, Reboot UPS
Gracefully, or Put UPS To Sleep Gracefully in the control console