User`s guide

®
USER’S GUIDE
Network Management Card
31
Synchronized Control Group guidelines
The following guidelines apply to Synchronized Control Groups:
All UPSs in a Synchronized Control Group must be the same model.
Synchronized Control Groups are supported for any Smart-UPS or Symmetra UPS
with a card slot that accepts a Network Management Card.
In a Synchronized Control Group of Symmetra 3-phase UPSs, the shutdown mode
(set at the UPS) must be either Normal or Secure for each UPS.
The synchronization process
If you apply an action to a Synchronization Control Group, enabled members of the
group behave as follows:
Each UPS receives the command regardless of output status (e.g, low battery).
The action uses the delay periods (such as Shutdown Delay, Sleep Time, and
Return Delay) configured for the initiating UPS.
When the action begins, a UPS that is unable to participate retains its present output
status while the other UPSs perform the action. If a UPS is already in an output state
that the action requires (e.g., a UPS is already off when the Reboot UPS action
starts), that UPS logs an event, but performs the rest of the action, if any.
All participating UPSs synchronize their performance of the action (within a one-
second time period under ideal conditions for Smart-UPS, but sometimes longer,
especially for Symmetra UPSs).
To configure a Management Card to be a member of a Synchronized Control
Group, see The Sync Control Option.