User`s guide
®
USER’S GUIDE
Network Management Card
8
Features
AP9618 or AP9619 Description
9-pin connector
1
• Output relay (Output): Normally closed (NC), common (COM),
and normally open (NO) pins. These pins are used by the
Integrated Environmental Monitor to interface to attached alarm
systems, annunciators (such as lights, beacons, bells, and
buzzers), controllers, HVAC thermostat lines, and similar
devices. They are rated for a switching capacity of 1A 30V AC/
DC.
•Power (Pwr): Normally-open ground (GND NO) and +12VDC
pins
can provide up to 25mA of power to devices such as smoke
and motion sensors.
• Input contacts (Zone 1 and 2): Two dry contact inputs. Each
zone can be connected to normally open (NO) contacts, normally
closed (NC) contacts or a combination (COM) of the two. See
Sensor Zone Connections (AP9618 and AP9619 only) for details
Possible applications include magnetic contact switches; tamper
switches; and water, pressure, and smoke sensors.
Probe connector
1
Connects a temperature/humidity sensor (probe) to the Integrated
Environmental Monitor.
AP9618 only Description
Modem connector
2
Connects the internal analog modem to an analog phone line to
provide for out-of-band communications.
AP9617, AP9618, AP9619 Description
Reset button Resets the Management Card while power remains on.
10/100 Base-T connector Connects the Management Card to the Ethernet network.
Status LEDs See Status LED.
Link-RX/TX (10/100) LED See Link-RX/TX (10/100) LED.
1. To manage the Integrated Environmental Monitor, see Environmental Monitoring.
2. To configure this feature for dial-in access to the control console at an AP9618 Network Management