Specifications

NetShelter SX Cabinet - Installation and Customization Manual16
2. Move the mounting flange to the desired location. Vertical
mounting flanges adjust in 6 mm (1/4 in.) increments.
3. To align the vertical mounting flange, note the symbol
(for example, a diamond) visible through one of the three
holes. Only one symbol will be visible. In the factory
standard position, a circle symbol is visible.
Make sure the same symbol is visible through the
corresponding hole at both the top and the bottom of the
flange.
4. When the vertical mounting flange is in the desired location
at the top, middle, and bottom, raise the flat bracket to the
lock position. The teeth in the bracket will engage fully with
the teeth in the side brace . Tighten the TORX screws .
Note: On the 750 mm rack, there are circle symbols 476 mm (18.75 in.) behind the front mounting flange. These
circle symbols designate rear vertical mounting flange positions required for installation of particular networking and
telecommunications equipment.
ns1623a
ns0718a
ns2292a