Specifications
NetShelter SX Cabinet - Installation and Customization Manual14
Equipment Installation
Note: NetShelter SX cabinets are intended for use with Listed equipment. If you install un-Listed equipment, you
should evaluate the safety of your configuration.
Adjust the Vertical Mounting Flanges
Vertical mounting flanges come factory-installed at 737 mm
(29 in.), the proper location for use with rack-mountable equipment.
The mounting flanges are adjustable towards the front or the rear of the
cabinet to accommodate different rails or equipment with other depths.
A common application for the 750 mm (29.5 in.) wide cabinet is to move the
flanges to a depth of 476 mm (18.75 in.) to accommodate networking and
telecommunications equipment.
Position the Vertical Mounting Flanges
WW
D
D
a
b
c
ns2293a
Accessory Channel
Top View
• Configuration 1: The Accessory Channel is installed. The Vertical
Mounting Flanges can be installed a minimum distance of (a) and
can extend as far as (b).
• Configuration 2: The Accessory Channel is removed. The Vertical
Mounting Flanges can extend as far as (c).
Cabinet
Width (W)
Cabinet
Depth (D) a b c
600 mm 1070 mm
190 mm
(7.5 in.)
787 mm
(30.75 in.)
921 mm
(36.25 in.)
750 mm 1070 mm
285 mm
(11.25 in.)
787 mm
(30.75 in.)
921 mm
(36.25 in.)
600 mm 1200 mm
190 mm
(7.5 in.)
787 mm
(30.75 in.)
1047 mm
(41.25 in.)
750 mm 1200 mm
285 mm
(11.25 in.)
787 mm
(30.75 in.)
1047 mm
(41.25 in.)
ns1621b