Specifications
4 Rack Access PX-HID Installation
Installation
Rack Access PX-HID
You can install the Rack Access PX-HID in the
front or the rear of the enclosure using the
rack-mount option, which uses 1 U of enclosure
space. You can install the Rack Access PX-HID in
the rear of the enclosure using the toolless
peg-mount option, which does not use any
U-spaces. The toolless peg-mount option is
available only with APC enclosures.
Toolless peg-mount installation.
1. Slide both mounting pegs into the holes
located in the cable channel in the rear panel of
the enclosure.
2. Snap the Rack Access PX-HID into place by
pushing it downward until it locks into
position.
Rack-mount installation.
1. Remove the toolless mounting pegs located at
the front of the unit.
2. Attach the power cord retainer to the end of
the Rack Access PX-HID that is closest to the
AC Line Inlet, then attach the brackets
(provided) to the Rack Access PX-HID, using
two of the provided screws for each bracket.
This option may not be available with
all enclosures.
aem0049a
a
e
m
0
0
8
7