User`s guide

58NetBotz Appliance User’s Guide
Configuring periodic FTP reports
To configure your appliance to periodically generate and deliver sensor reports to a specified FTP server:
1. Select Periodic FTP Report from the Periodic Reports Configuration window and click Edit.
2. The Edit Periodic FTP Report window opens. This window contains the following fields:
Field Description
Enabled Enable periodic FTP reporting.
Include camera
pictures
Include image captures by camera pods connected to the appliance
in the FTP post. Image captures included with periodic reports are
640x480 resolution, regardless of appliance Camera settings.
Include maps Include maps stored on the appliance in the FTP post.
Include graphs Include graphs of the sensor readings for all sensors associated
with the appliance in the FTP post.
Interval The frequency in minutes with which FTP reports are generated.
Sensor priority Limit the amount of sensor data included with the periodic report.
Select one of the following settings:
High: Only sensor data associated with physical sensors that are
integrated with or connected to the appliance are included in the
report. Sensor data associated with remote devices is not included
in the report.
Medium: Sensor data associated with physical sensors and with
Advanced Data sensor sets from remote devices is included in the
report. Data not included in the report is data associated with
remote devices that is not grouped in an Advanced Data sensor
set.
Low: Sensor data from all sensors is included in the report.
Graph priority Limit the amount of sensor data included with the periodic report.
Select one of the following settings:
High: Only sensor data associated with physical sensors that are
integrated with or connected to the appliance is included in the
report. Sensor data associated with remote devices is not included
in the report.
Medium: Sensor data associated with physical sensors and with
Advanced Data sensor sets from remote devices is included in the
report. Data not included in the report is data associated with
remote devices that is not grouped in an Advanced Data sensor
set.
Low: Sensor data from all sensors is included in the report.
Graph available
history
The maximum time period for which data is graphed.
FTP hostname The hostname or IP address of the FTP server to which the report is
delivered.
User name The user ID to access the specified FTP server.
FTP password The password to access the specified FTP server.
Verify password Type the FTP Password to confirm the password.