User`s guide
141NetBotz Appliance User’s Guide
the appliance is configured to generate alert states and send alert notifications as efficiently as
possible.
• When viewing alerts in Advanced View, setting the refresh interval to None or to a high refresh
interval allows a heavily-alerting appliance to load its list of alerts more efficiently.
• Do not leave Advanced View and/or Basic View up and running with the Cameras view selected
when it is not being used. Streaming of interactive camera pictures from appliances consumes
appliance resources.
• Upgrade your appliances only when the alert load on an appliance is low.
• Select a shorter capture time or less total picture capture size to prevent multiple overlapping alert
picture captures and to store a greater number of alert captures before they are deleted to make
room for more recent alert captures.
• If your appliance is managed by an InfraStruXure Central server and has surveillance enabled
through InfraStruXure console, configure the surveillance to record lower frame rates and/or
resolutions to reduce load on the appliance. Also consider disabling audio with surveillance
footage, as this increases the load on the appliance.