ALERTSENSORVALUEUNITS The units used for the sensor value. Currently defined
units include:
• NONE - None
• DEGREESC - Degrees C
•DEGREESF - Degrees F
•PERCENT - Percent
• FT_MIN - Feet/Minute
• M_MIN - Meters/Minute
• AMPS - Amps
Future units values are limited to 8 characters.
ALERTSENSORLABEL The label associated with the specific sensor. This field
is limited to 64 characters.
AGENTIP The dotted decimal IP address of the device being
monitored. This field is only defined for alerts
concerning sensors or attributes directed at devices other
than the NetBotz device itself (i.e. devices monitored by
MIB-2 scanners).
AGENTHOSTNAME The hostname of the device being monitored. This field
is only defined for alerts concerning sensors or attributes
directed at devices other than the NetBotz device itself
(i.e. devices monitored by MIB-2 scanners). This field is
limited to 64 characters.
ALERTSENSORLOC_ENCLOSUREID Enclosure ID of enclosure containing the alarming
sensor, if different than the NetBotz device.
ALERTSENSORLOC_SLOTLOCATION Slot ID within enclosure where the alarming sensor is
located, if different than the NetBotz device.
ALERTSENSORLOC_ENCLOSURERELLOC Relative location of alarming sensor within enclosure.
This is intended to be one of a well defined set of
common locations, as defined below:
• ABOVE – on top of exterior of the enclosure
• BELOW – below the bottom of the enclosure
• CENTERINTERIOR – middle third of the interior of
the enclosure
• TOPINTERIOR – top third of the interior of the
enclosure
• BOTTOMINTERIOR – bottom third of the interior of
the enclosure
• LEFTPOWER – left side power rail for enclosure
• RIGHTPOWER – right side power rail for enclosure
• AIRINTAKE – at the air intake for the enclosure
• AIREXHAUST – at the air exhaust for the enclosure
• FRONTDOOR – at the front door of the enclosure
• BACKDOOR – at the back door of the enclosure
• ATUPS – at the UPS for the enclosure
• ATCOOLING – at the cooling system for the enclosure
• ATPDU – at the power distribution unit for the
enclosure
ALERTSENSORLOC_ROOM Room number where the alarming sensor is located, if
different than the NetBotz device.