Specifications
17MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
Battery Run-Times - Non-Modular Batteries
• The below battery run-times are based on high quality batteries from approved manufacturers
• The run-times are based on high rate batteries designed for UPS systems
• The run-times are intended as a guide only, and APC disclaim the responsibility for these run-
times
10 kVA
15 kVA
Battery Ah Load %
20 hr rate
Ah
Approx.
equivalent
10 hr rate
Ah
40 50 60 70 80 90 100
7.2 6.7 24 18 14 11 9 7 6
11 10 42 32 25 20 17 14 12
15 14 63 48 38 31 26 22 19
20 19 90 69 55 46 39 33 29
24 22 113 87 70 58 49 42 37
30 28 149 115 92 77 65 56 49
38 35 199 154 124 103 88 76 67
Battery Ah Load %
20 hr rate
Ah
Approx.
equivalent
10 hr rate
Ah
40 50 60 70 80 90 100
11 10 25 19 14 11 9 7 6
15 14 38 29 22 18 15 13 11
20 19 55 42 33 27 23 19 17
24 22 70 53 42 35 29 25 21
30 28 92 70 56 46 39 34 29
38 35 124 95 76 63 53 46 40
50 47 174 133 107 89 75 65 57
0
10
20
30
40
50
60
70
80
90
100
110
120
40 60 80 100
Load %
Runtime [Minutes]
2x16x12V/7.2(6.7)Ah
2x16x12V/11(10)Ah
2x16x12V/15(14)Ah
2x16x12V/20(19)Ah
2x16x12V/24(22)Ah
2x16x12V/30(28)Ah
2x16x12V/38(35)Ah
0
10
20
30
40
50
60
70
80
90
100
110
120
40 60 80 100
Load %
Runtime [Minutes]
2x16x12V/11(10)Ah
2x16x12V/15(14)Ah
2x16x12V/20(19)Ah
2x16x12V/24(22)Ah
2x16x12V/30(28)Ah
2x16x12V/38(35)Ah
2x16x12V/50(47)Ah