4. Run a terminal program such as HyperTerminal, and configure the selected port for
9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
5. Press
ENTER to display the User Name prompt.
6. Enter the Administrator user name and password (apc by default for both).
7. From the Control Console menu, select System, then Tools, then File Transfer,
then XMODEM; and type Yes at the prompt to continue.
8. Select a baud rate, change the terminal program’s baud rate to match your
selection, and press
ENTER. A higher baud rate causes faster upgrades.
9. From the terminal program’s menu, select the binary AOS file to transfer using
XMODEM-CRC. After the XMODEM transfer is complete, set the baud rate to 9600.
The Rack PDU automatically restarts.
10.Repeat step 4 through step 4 to install the application module. In step 9, use the
application module file name, not the AOS module file name.
For information about the format used for firmware modules, see
Firmware files (Rack PDU).