SCP. To use Secure CoPy (SCP) to upgrade firmware for a Rack PDU:
1. Identify and locate the firmware modules described in the preceding instructions for
FTP.
2. Use an SCP command line to transfer the AOS firmware module to the Rack PDU.
The following example uses xxx to represent the version number of the AOS
module:
scp apc_hw03_aos_xxx.bin apc@158.205.6.185:apc_hw03_aos_xxx.bin
3. Use a similar SCP command line, with the name of the application module, to
transfer the second firmware module to the Rack PDU.
How to upgrade multiple Rack PDUs
Export configuration settings. You can create batch files and use an APC utility to
retrieve configuration settings from multiple Rack PDUs and export them to other Rack
PDUs.
Use FTP or SCP to upgrade multiple Rack PDUs. To upgrade multiple Rack PDUs
using an FTP client or using SCP, write a script which automatically performs the
procedure.
Use XMODEM to upgrade one Rack PDU
To upgrade the firmware for a Rack PDU that is not on the network:
1. Obtain the individual firmware modules (the AOS module and the application
module) from www.apc.com/tools/download.
2. Select a serial port at the local computer and disable any service that uses the port.
3. Connect the provided serial cable (APC part number 940-0144) to the selected port
and to the serial port at the Rack PDU.
See also
See Release Notes: ini File Utility, version 1.0, available on the APC Metered
Rack PDU Utility CD.