User`s guide

®
USER’S GUIDE
Metered Rack PDU
89
The Upload Event and Error Messages
The event and its error messages
The following system event occurs when the receiving Rack PDU completes using the
.ini file to update its settings.
Configuration file upload complete, with number valid values
This event has no default severity level.
If a keyword, section name, or value is invalid, the event text is extended to include
notification of the following errors.
Event text Description
Configuration file warning: Invalid
keyword on line number.
Configuration file warning: Invalid
value on line number.
A line with an invalid keyword or value is ignored.
Configuration file warning: Invalid
section on line number.
If a section name is invalid, all keyword/value pairs
in that section are ignored.
Configuration file warning:
Keyword found outside of a
section on line number.
A keyword entered at the beginning of the file (i.e.,
before any section headings) is ignored.
Configuration file warning:
Configuration file exceeds
maximum size.
If the file is too large, the Rack PDU stores and
processes what it can, but ignores what it cannot.
Reduce the size of the file, or divide it into two files,
and try uploading again.
Note
The export to and the subsequent upload by the receiving Rack PDU
succeeds even if there are errors.