Setting the Low Load Warning Threshold
The default setting for the Low Load Warning Threshold is 0 Amps. This effectively
disables the warning. With a setting of 0 Amps for the Low Load Warning
Threshold, the Web interface will not indicate that a circuit breaker may have
tripped.
A 2-Amp detection threshold will help to indicate that a circuit breaker may have
tripped.
Web interface.
1. Select the Device Manager tab, or click More in the Load Status section of the
Home page.
2. Set the Low Load Warning Threshold for each bank or phase to 2 Amps.
3. Click Apply in each bank or phase section to set the selected values.
Note
With factory default settings, the Rack PDU generates a warning
alarm when any bank exceeds 16 Amps, and generates a critical
alarm when any bank exceeds 20 Amps. However, if a circuit
breaker trips, there is no definitive indication that the circuit
breaker is open, other than that the current for that bank will drop.
Set the Low Load Warning Threshold to 2 Amps for these
reasons: