Outlet Name Configuration (High Density PDUs only)
Edit the name of each outlet and click Apply to save changes or Cancel to exit without
saving the changes.
Rack PDU Settings
Configuring load thresholds
Web interface.
1. Select the Device Manager tab from the navigation menu. The Load Management
left navigation menu option opens by default when the Device Manager tab is
selected.
2. Set the thresholds for each phase or bank. The configurable thresholds are
Overload Alarm Threshold, Near Overload Warning Threshold, and Low Load
Warning Threshold for each phase or bank.
3. Click Apply to set the selected values.
Control console.
1. From the Device Manager menu, select Phase Management/Bank Management.
2. Select a phase or bank (for 3-phase units).
3. Select a threshold to configure: Overload Alarm Threshold (amps), Near
Overload Warning Threshold (amps), or Low Load Warning Threshold (amps).
4. Select Accept Changes.
To set the low load warning threshold, see Setting the Low Load
Warning Threshold.
Setting Description
Overload Alarm
Threshold
Set the number of amps that will cause an overload of this phase
or bank.