User`s guide

®
®®
®
USERS GUIDE
masterswitch plus
57
Outlet Properties Menu
Overview
MasterSwitch Plus has eight Outlet Properties menusone for each
outlet. To access these menus, enter an outlet number (1– 8) from the Main
menu. The Outlet Properties menu varies according to the Outlet Control
mode setting of the chosen outlet.
Graceful Shutdown menu items
Item Definition
Outlet Name Identifies each outlet.
Outlet Control
Mode
Establishes mode for associated outlet.
Will Device
Confirm
Indicates whether the device connected to the outlet can assert a
shutdown signal.
Low Battery
Warning
Control
Selects the method MasterSwitch Plus uses for determining when to
assert the outlet’s Low Battery signal after the UPS has switched to
battery operation.
UPS Low
Battery
Multiplier
A low battery signal is generated when the UPS's remaining battery
runtime falls below this value multiplied by the UPS Low Battery
Warning.
Restart Delay
The delay between removing power from an outlet due to a Graceful
Shutdown and reapplying power to that outlet.
Power Off
Delay
The time from the triggering event (such as a server confirming a
shutdown) until power is removed from the outlet.
Power On
Delay
Determines the time interval between the triggering event and power
being applied to the outlet.
Reboot
Duration
The delay between removing power from an outlet because of a reboot
and reapplying power to an outlet.