User`s guide
®
®®
®
USER’S GUIDE
masterswitch plus
12
MasterSwitch Plus Status LED
Manual button
The Manual button is used to cancel two different commands. If this button
is pressed for at least
1
/
2
second and then released, one of the following
results will occur:
• If the MasterSwitch Plus is waiting for the Master Power On Delay to
expire, MasterSwitch Plus will issue a cancel command. The diagram
in Unit/Outlet start-up sequence illustrates the outlet’s behavior when
the Master Power On Delay is cancelled.
• If the configuration contains a UPS and the UPS is operating on AC
power, then MasterSwitch Plus will issue a Battery Capacity Override
command. The diagram in Unit/Outlet start-up sequence illustrates the
outlet’s behavior when the Battery Capacity Override command is
issued.
If neither of the above conditions are true, pressing the Manual button will
have no effect.
LED State Definition
Off
MasterSwitch Plus has no power.
Solid green
MasterSwitch Plus has valid network settings.
Flashing green
MasterSwitch Plus does not have valid network settings. See
the Installation Manual for more information.
Flashing red
slowly
MasterSwitch Plus is making a BOOTP request.
Solid red
MasterSwitch Plus has detected a hardware failure.