Upgrading Firmware
You can use a local computer that connects to the unit through the serial
port on the front panel of the unit.
1. Select a serial port at the local computer, and disable any service
which uses that port.
2. Use the supplied smart-signaling cable (940-0024C) to connect the
selected port to the serial port on the front panel of the unit.
3. Run a terminal program (such as HyperTerminal) and configure the
selected port for 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow
control. Save the changes.
4. Press
ENTER twice to display the User Name prompt.
5. Enter your user name and password (both apc, for administrators only)
and press the Enter key.
6. From the Control Console menu, select System, then Tools, then
XMODEM.
7. At the prompt Perform transfer with XMODEM-CRC? type yes,
and press
ENTER.
8. The system will then prompt you to choose a transfer rate and to
change your terminal settings to match the transfer rate. Press
ENTER
to set the MasterSwitch Plus to accept the download.
9. In the terminal program, send the file using the XMODEM protocol.
Upon completion of the transfer, the console will prompt you to restore
the baud rate to normal.
S
ee also
For a complete description of how to download a firmware
upgrade for your MasterSwitch Plus, see the Management
Card Addendum (.\MS_PLUS\Addendum.pdf) on the
provided APC MasterSwitch Utility CD.