User Manual

Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower10
Nominal Output
Vo l ta ge
100 Vac N/A
230 Vac models only: Set the nominal output voltage of
the UPS to standby mode.
120 Vac N/A
230 Vac
220 Vac
230 Vac
240 Vac
Transfer Sensitivity Normal Normal, Reduced, Low
Select the level of sensitivity to power events that the
UPS will tolerate.
Normal: The UPS will go on battery power more
often to provide the cleanest power supply to the
connected equipment.
Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power disturbances,
set the sensitivity to Normal.
Low Battery Alert 120 sec Set the value in seconds
The UPS will emit an audible alarm when the remaining
runtime has reached this level.
Date of Last Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off
The UPS will mute all audible alarms if this is set to Off
or when the display keys are pressed.
Battery
Self-Test Interval
Setting
On start up and every
14 days since the last
test
•Never
Start up only
Frequency of test
(every 7 to 14 days)
The interval at which the UPS will execute a
self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description