Specifications
86 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
1.2 DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by Schneider Electric.
1. Model: __________________________________________.
2. Total net cooling capacity: ___________________________ MBH (kW).
3. Sensible net cooling capacity: ________________________ MBH (kW).
4. Return air temperature: _____________________________ ºC (ºF) DB.
5. Return air temperature: _____________________________ ºC (ºF) WB.
6. Entering chilled water temperature:____________________ºC (ºF) WB.
7. Humidity: _______________________________________% RH.
8. Air quantity: _____________________________________ L/s (CFM).
9. External Static Pressure:____________________________Pa (in.).
10. Reheat capacity:__________________________________kW (MBH).
11. Humidifier capacity: _________________ _____________ kg/hr (lbs/hr) (ACRP500 series only).
12. Electrical supply: ________ ______V, ________________ ph, 50/60 Hz.
1.3 SUBMITTALS
A. Submittals are provided with the proposal and shall include: capacity data, electrical data, physical
data, electrical connection drawing, and piping connection drawing.
1.4 QUALITY ASSURANCE
A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not be
limited to the following: complete pressure and leak testing to ensure system integrity, “Hi-Pot” test,
and controls calibration and settings. Each system shall ship with a completed test report to verify
completion of factory testing procedure. The system shall be NTRL listed, MCA, and UL Listed to UL
1995 and CSA 22.2 No. 236.
1.5 WARRANTY
A. System parts shall be warranted for a period of 18 months from date of shipment and 12 months from
startup. Optional extended warranties are available.